For Non-Health Hazard Applications
ES-757DCDA/757NDCDA
Job Name
–––––––––––––––––––––––––––––––––––––––––––
Contractor
––––––––––––––––––––––––––––––––––––––––––––
Job Location
–––––––––––––––––––––––––––––––––––––––––
Approval
–––––––––––––––––––––––––––––––––––––––––––––
Engineer
–––––––––––––––––––––––––––––––––––––––––––––
Contractor’s P.O. No.
––––––––––––––––––––––––––––––––––
Approval
–––––––––––––––––––––––––––––––––––––––––––––
Representative
––––––––––––––––––––––––––––––––––––––––
Series 757DCDA,
757NDCDA
Double Check Detector Assemblies
Sizes: 2
1
/2" – 10" (65 – 250 mm)
Series 757DCDA, 757NDCDA Double Check Detector
Assemblies are used to prevent backflow of non-health hazard
pollutants that are objectionable but not toxic, from entering
the potable water supply system. The 757DCDA, 757NDCDA
may be installed under continuous pressure service and may
be subjected to backpressure and backsiphonage. Series
757DCDA, 757NDCDA is used primarily on fire line sprinkler
systems when it is necessary to monitor unauthorized use of
water.
Features
Extremely compact design
70% Lighter than traditional designs
304 (Schedule 40) stainless steel housing & sleeve
Groove fittings allow integral pipeline adjustment
Patented tri-link spring check provides lowest pressure loss
Unmatched ease of serviceability
Available with grooved butterfly valve shutoffs
May be used for horizontal, vertical or N pattern installations
Replaceable check disc rubber
Specifications
The Double Check Detector Assembly shall consist of two
independent tri-link check modules within a single housing,
sleeve access port, four test cocks and two drip tight shutoff
valves. Tri-link checks shall be removable and serviceable, with-
out the use of special tools. The housing shall be constructed
of 304 Schedule 40 stainless steel pipe with groove end con-
nections. Tri-link checks shall have reversible elastomer discs
and in operation shall produce drip tight closure against reverse
flow caused by backpressure or backsiphonage. The bypass
assembly shall consist of a meter, which registers in either gal-
lon or cubic measurement, a double check backflow assembly
and required test cocks. Assembly shall be a Watts Regulator
Company Series 757DCDA, 757NDCDA.
757DCDAOSY
757NDCDAOSY
757DCDABFG
Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,
please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with-
out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.
Vue de la page 0
1 2 3 4

Résumé du contenu

Page 1 - 757NDCDA

For Non-Health Hazard ApplicationsES-757DCDA/757NDCDAJob Name ––––––––––––––––––––––––––––––––––––––––––– Contractor –––––––––––––––––––––––––––

Page 2 - Dimensions — Weight

HAIJGP C DMaterialsHousing & Sleeve: 304 (Schedule 40) Stainless SteelElastomers: EPDM, Silicone and Buna-NTri-link Checks: Noryl®, Stainless Stee

Page 3 - 2" (65mm)

CapacitySeries 757DCDA, 757NDCDA flow curves as tested by Underwriters Laboratory per UL 1469, 1996.Flow characteristics collected using butterfly shu

Page 4

For additional information, visit our web site at: www.watts.comES-757DCDA_757NDCDA 1151 © 2012 WattsUSA: Tel. (978) 688-1811 • Fax: (978) 794-1