8550 Hansen Road Houston, Texas 77075 (Ph) 713.943.0688 (Fx) 713.944.9445 www.wattsacv.com
01/05
R
Stainless Series
S116-5 or S6116-5 (Globe)
S1116-5 or S61116-5 (Angle)
Operation
The Watts ACV Combination Backpressure or Sustaining Control Valve with Hydraulic Check Feature is
designed to permit flow when upstream pressure is above the adjustable setpoint of the control pilot, and
throttle toward closed when upstream pressure falls below the adjustable setpoint, and close drip-tight when
downstream pressure becomes greater than upstream pressure.
It is controlled by a normally closed control pilot designed to: 1) Open (allowing fluid out of the main valve
cover chamber) when upstream pressure is above the adjustable setpoint, and, 2) Close (allowing fluid to
fill the main valve cover chamber) when upstream pressure is below the adjustable setpoint. An increase in
upstream pressure causes the valve to modulate toward an open position. A decrease in upstream pressure
causes the valve to modulate toward a closed position.
If downstream pressure becomes greater than upstream pressure, downstream pressure is admitted to
the main valve cover chamber, closing the valve and preventing reversal of flow. Normal backpressure or
sustaining operation resumes when upstream pressure exceeds downstream pressure.
When the valve is installed “in line” on the discharge of a pump, it acts as Backpressure Control Valve.
When pump discharge pressure falls below the pilot setting, the valve modulates toward a closed position,
increasing backpressure against the pump. The valve should be specified to include the optional opening
speed control when used for Backpressure applications.
When the Model valve is located “in line” connecting two distribution zones, the valve acts as a Pressure
Sustaining Control Valve. When pressure in the upstream zone falls below the pilot setting, the valve
modulates toward a closed position, sustaining pressure in the upstream zone. The valve will close, if
necessary, until upstream pressure is above the pilot setting. The valve should be specified to include the
optional opening speed control and position indicator when used for Pressure Sustaining applications.
BACKPRESSURE SUSTAINING VALVE
with HYDRAULIC CHECK FEATURE
BACKPRESSURE SUSTAINING VALVE
with HYDRAULIC CHECK FEATURE
Vue de la page 0
1 2

Résumé du contenu

Page 1 - Stainless Series

8550 Hansen Road • Houston, Texas 77075 • (Ph) 713.943.0688 • (Fx) 713.944.9445 • www.wattsacv.com01/05RStainless SeriesS116-5 or S611

Page 2

8550 Hansen Road • Houston, Texas 77075 • (Ph) 713.943.0688 • (Fx) 713.944.9445 • www.wattsacv.com01/05RStainless SeriesS116-5 or S611

Modèles reliés S116-5

Commentaires sur ces manuels

Pas de commentaire