Installation, Maintenance, & Repair
Series 007 and LF007
Double Check Valve Assemblies
Sizes:
1
2" – 3" (15 - 80mm)
NOTICE
For Australia and New Zealand, line strainers should be installed
between the upstream shutoff valve and the inlet of the backflow
preventer.
3
4" 007M3QT
RP/IS-007
Watts product specifications in U.S. customary units and metric
are approximate and are provided for reference only. For precise
measurements, please contact Watts Technical Service. Watts
reserves the right to change or modify product design, construc-
tion, specifications, or materials without prior notice and without
incurring any obligation to make such changes and modifications
on Watts products previously or subsequently sold.
Testing
For field testing procedure, refer to Watts installation sheets
IS-TK-DP/DL, IS-TK-9A, IS-TK-99E and IS-TK-99D found on
www.watts.com.
For other repair kits and service parts, refer to our Backflow
Prevention Products Repair Kits & Service Parts price list PL-RP-
BPD found on www.watts.com.
For technical assistance, contact your local Watts representative.
Local building or plumbing codes may require modifications to the
information provided. You are required to consult the local building
and plumbing codes prior to installation. If this information is not
consistent with local building or plumbing codes, the local codes
should be followed.
Need for Periodic Inspection/Maintenance: This product must
be tested periodically in compliance with local codes, but at least
once per year or more as service conditions warrant. Corrosive
water conditions, and/or unauthorized adjustments or repair could
render the product ineffective for the service intended. Regular
checking and cleaning of the product’s internal components helps
assure maximum life and proper product function.
WARNING
!
Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use information
can result in death, serious personal injury, property
damage, or damage to the equipment.
Keep this Manual for future reference.
Installation Instructions
Series 007 and LF007
1
2" - 2" (15 - 50mm)
Indoors - Figure 1
Check local codes for installation requirements. Pipe lines should
be thoroughly flushed to remove foreign material before installing
the unit. A strainer should be installed as shown, ahead of backflow
preventer to prevent disc from unnecessary fouling. Install valve
inline with arrow on valve body pointing in the direction of flow.
For indoor installations, it is important that the valve be easily acces-
sible to facilitate testing and servicing. Do not install in a concealed
location.
CAUTION
!
Do not install with strainer when backflow preventer is used on
seldom-used water lines which are called upon during emergen-
cies, such as fire sprinkler lines, etc.
It is important that Series 007 and LF007 be tested periodically in
compliance with local codes, but at least once a year or more often
depending upon system conditions. Regular inspection, testing and
cleaning assures maximum life and proper product function.
NOTICE
Fire Protection System Installations
The National Fire Protection Agency (NFPA) Guidelines require a
confirming flow test to be conducted whenever a “main line” valve
such as the shutoff valves or a backflow assembly have been oper-
ated. Certified testers of backflow assemblies must conduct this
test. The trim valves of the confirming flow test. When the test is
completed, the trim valves must be returned to a fully open position.
Meter Box Installation
Vue de la page 0
1 2 3 4

Résumé du contenu

Page 1 - Series 007 and LF007

Installation, Maintenance, & Repair Series 007 and LF007Double Check Valve AssembliesSizes: 1⁄2" – 3" (15 - 80mm)NOTICEFor Australia and

Page 2 - Service and Maintenance

Installation InstructionsSeries 007 and LF0071⁄2" - 2" (15 - 50mm)Service and MaintenanceServicing the First and Second Check Valves NOTICEB

Page 3

3Indoors - Figure 4Series 007 may be installed in either a vertical or horizontal posi-tion. Pipe lines should be thoroughly flushed to remove for-eig

Page 4 - ⁄2" and 3"

Servicing First and Second Check ValvesSeries 007 and LF00721⁄2" and 3" SeatSeat O-ringDisc AssemblySpring RetainerCaps/ SeatCoverCover O-ri