Vue de la page 0
8550 Hansen Road Houston, Texas 77075 (Ph) 713.943.0688 (Fx) 713.944.9445 www.wattsacv.com
01/05
R
Classic Series
Operation
The Watts ACV Pump Control Valve is designed to minimize the surges associated with the starting and
stopping of pumps. The valve slowly opens and closes as required to control pumping related surges. The
pump starts and stops against a closed valve.
Pump start up: When the pump is signaled to start, the 4-Way Solenoid is energized and directs fluid and
pressure into the power chamber (below the diaphragm), and relieves fluid and pressure from the cover
chamber (above the diaphragm). The fluid and pressure relieved from the cover chamber is vented to
atmosphere or available floor drain. The valve opens at an adjustable rate, gradually admitting pumping
pressure into the distribution system. Rate of valve opening is controlled by the adjustable opening speed
control, which restricts the speed at which fluid and pressure evacuate the cover chamber. The valve
remains fully open during the pumping cycle.
Pump shutdown: When the pump is signaled to shut-off, the 4-Way Solenoid is de-energized, and directs
fluid and pressure into the cover chamber (above the diaphragm), and relieves fluid and pressure from the
power chamber (below the diaphragm). The fluid and pressure relieved from the power chamber is vented
to atmosphere or available floor drain. The valve closes at an adjustable rate, gradually reducing pumping
pressure. Rate of valve closure is controlled by the adjustable closing speed control, which restricts the
speed at which fluid and pressure evacuate the power chamber. When the valve reaches the closed position,
the limit switch is actuated, turning the pump off.
Emergency Closure: The valve is equipped with a Mechanical Check Feature, which acts independent of
diaphragm position, and provides immediate closure when flow ceases.
Manual Operation: Engaging the Solenoid Manual operator simulates power to the solenoid, manually
opening the main valve. Disengaging the Solenoid Manual operator returns the valve to the closed
position.
F513-5 (Globe)
F1513-5 (Angle)
PUMP CONTROL VALVE with
MECHANICAL CHECK FEATURE
Vue de la page 0
1 2

Résumé du contenu

Page 1 - Classic Series

8550 Hansen Road • Houston, Texas 77075 • (Ph) 713.943.0688 • (Fx) 713.944.9445 • www.wattsacv.com01/05RClassic SeriesOperationThe Wat

Page 2

8550 Hansen Road • Houston, Texas 77075 • (Ph) 713.943.0688 • (Fx) 713.944.9445 • www.wattsacv.com01/05RClassic SeriesInstallation Gui

Modèles reliés F513-5

Commentaires sur ces manuels

Pas de commentaire